Ideal Classic Sealed System Not Working

I got called to look at an Ideal Classic Sealed System boiler which was not working for the central heating. The hot water was heated by an immersion element only, and the boiler is only used for the central heating.

I ensured the programer was on and the room thermostat turned up to call for heat. I also ensured the boiler was switched on. I could hear that the pump was running but there was no noise from the boiler. I removed the case and could smell that the fan had been overheating. I checked to make sure there was 240 volts at the fan which there was.

I replaced the fan and the boiler was working fine again.