I replaced the fan with the correct version and the boiler was working fine again.
There are two different fans for different versions of the boiler which look similar. The obvious difference between the fans being the terminal positions. On one version the terminals are both on the left hand side of the fan motor and the wiring loom is shorter for these terminals. On the other version, the terminals are on opposing sides of the fan motor as you look at the fan motor from the front and the grey wires are longer in this case. There are other fans for other versions of the Ideal Classic as well such as the NF30-80.
It is also important to remember to slide the flue back together correctly. If the inner flue is not connected back up the boiler will baffle out when it lights and the boiler will cycle on and off.