I looked inside the cover of the Boilermate 2000 cylinder and could see that the display on the PCB was blank, although two of the green LEDs were lit and two of the pumps were running. Pushing the little buttons on the PCB to toggle through the displays of the circuit board was not having any effect. For some reason the PCB had failed and was no demanding heat from the boiler or operating the boiler pump. There was no GT155 PCB in stock locally or available next day from our suppliers and had to be ordered for the following week.
I looked into the electrical side of the Boilermate Cylinder and could see that the immersion heater had been wired up, and that there was wiring to the cylinder for the electrical side. However, the fuses were pulled out and secured out with a cable tie and the electrical side had never been commisioned at installation. I advised the customer to contact and electrician to check the electrics which got the hot water heating again temporarily until I was able to return with a new PCB.
|