I tested the hot water and sure enough the boiler fired up and the system was running perfectly for hot water. I then turned the hot water off and put the central heating on and nothing happened. I checked in the junction box to make sure there was power on the grey and white wires to the motorised valve, which there was.
I then drained the system and replaced the Boss three-port valve with another motorised valve, refilled and heat tested the system and all was working well again.