Before I arrived I already had a good idea of what the problem could be. Firstly I checked that the 'kettle plug' electrical connection was fully in the control box connection. I removed the control box cover and checked for power on the switched live which there was. There was also power coming through the boiler thermostat and supplying power to the gas valve solenoid.
Sometimes the pilot lights can click out on the gas valve, but the pilot stay lit. I turned out the pilot light and relit it but this did not solve the problem. It left two options which was the gas valve or its solenoid. I had a replacement solenoid and so I replaced the solenoid. This solved the problem and the boiler was working well again.
Disclaimer:
The works described in this blog are a record of work undertaken and should not be taken as guaranteed to solve your problem.