I have seen this problem before on these boilers and so am always wary of believing what the pressure gauge says. I grabbed a bucket out of my van and a couple of manometer hoses and attached these to the drain plugs on the flow and return of the boiler. I drained the boiler through these drain plugs. Using a spanner I undid the gauge connection at the boiler and removed it from the boiler. The hole for the water that activates the pressure gauge is tiny and can only be unblocked with a fine pin. I unblocked the hole and re-assembled the boiler. Opening the filling loop I could see that the water pressure was rising and that the gauge was showing the correct reading again.
Disclaimer:
The works described in this blog are a record of work undertaken and should not be taken as guaranteed to solve your problem.
|
good to know as my boiler is the same. workiung fine for CH and DHW but guage showing 0 pressure. Cheers
ReplyDelete