Thursday, 19 April 2012

Hot Water Not Working

The central heating is working, but the hot water is not heating. I switched on the hot water at the timer, and had a look in the airing cupboard. There were two zone valves, and the hot water zone valve was making a slight buzzing noise, but the lever was not moving. I looked at the wiring centre, and there was power at the grey wire to the valve (permanent live) and the brown (calling from the cylinder thermostat).

The valve was a Honeywell V4043H two-port zone valve and the head was jammed, but the spindle was free to turn after the head was removed. I replaced the motorised valve head and the hot water began heating correctly.


Disclaimer:
The works described in this blog are a record of work undertaken and should not be taken as guaranteed to solve your problem.

Work should only be carried out by persons qualified and competent to do so.

No comments:

Post a Comment